PAUL SCHERRER INSTITUT
Diagnostic
PSI HomeGFA HomeABK HomeSLS HomeSLS Controls Home
Diagnostic
SLS Diagnostics
• DBPM-BO
• DBPM
• FOFB
• MBF
Proton Diagnostics
European X-FEL
SwissFEL
Intranet
Publications
Tools Inventory Database
KTRANS
DI ELOG

Author: Thomas Schilcher
Phone: +41 56 310 4593
Updated: 18.06.2019


Printer friendly version
 

[Validate HTML][Validate CSS]

SLS DBPM System




Operating Modes for SLS Storage Ring

Mode Description Digital
Downconverter
Output Rate
Bandwidth *)
turn-by-turn triggered mode,
turn-by-turn data,
up to 8192 turns available
1.0409 MHz550 kHz
ramp 250 ms triggered mode,
covers a time range of up to 251.8 ms
(8192 data points)
32.53 kHz15 kHz
ramp 500 ms triggered mode,
covers a time range of up to 503.6 ms
(8192 data points)
16.26 kHz7.5 kHz
ramp 2 s triggered mode,
covers a time range of up to 2.014 s
(8192 data points)
4.066 kHz0.69 kHz
closed orbit continuous data stream 4.066 kHz0.69 kHz


Single Bunch Performance of DBPM

intensity plot of ARIDI-BPM-12LD (Ibeam = 0 - 20 mA):
linear plot (postscript file)*)
only visible within PSI network

logarithmic plot (postscript file)*)
only visible within PSI network



*) only accessible within PSI network